Industrial LEL Calculator: %LEL and LOC Flammability of Gas Mixtures

This calculator determines the flammability of a waste gas stream by calculating the mixture's Lower Explosive Limit (LEL), also called the Lower Flammability Limit (LFL), and its Limiting Oxygen Concentration (LOC). Enter the composition, read the result, then use the reference sections below the calculator to interpret it.

The LEL of a mixture is the dilute limit of fuel that will sustain a flame. Fuel flammability is often reported as a percentage of LEL (%LEL). If a mixture is at or above 100 %LEL and has an oxygen concentration that is at or above the LOC, the mixture is flammable. Below 100 %LEL the gas is too lean to burn. Note that NFPA 86 states that mixtures above 25 %LEL require continuous vapor monitoring. Mixtures above 50 %LEL shall interlock the thermal oxidizer system such that the high LEL stream cannot be introduced to the hot combustion chamber.

The calculator also calculates the limiting oxygen concentration (LOC). The LOC is the minimum oxygen concentration in a fuel, air, and inert mixture that will propagate flame. LOC values are calculated using NFPA 69 B.8.1 Method 1.

To use the calculator, select the compounds and enter the vol% of each component in the waste gas mixture. Note the compound list included is not exhaustive, and that the calculated values are estimates evaluated at ambient conditions.

This calculator is not to be used for equipment design. Contact PCC for a detailed assessment of your waste gas stream.

%LEL and LOC Calculator

%LEL and LOC Calculator

Note that vol% does not need to add to 100%. Calculator will assume the balance is inert for purposes of calculating %LEL and LOC

Hidden LEL%

Hidden LEL%

Hidden LEL%

Hidden LOC%

Organic Vol%

%Vol Combustibles / LEL

%Vol Combustibles * COMBO2

Hidden MW Mol%

Start Over

What Do LEL, UEL, and LOC Mean?

  • The Lower Explosive Limit (LEL) is the lowest concentration of a fuel in air, by volume, that will propagate a flame. Below the LEL the mixture is too lean to burn. The Upper Explosive Limit (UEL) is the highest concentration that will burn; above it the mixture is too rich. The band between the two is the flammable range. Methane, for example, burns between 5.0 vol% and 15.0 vol% in air at ambient conditions.
  • LEL and LFL are the same number. NFPA 69 and NFPA 86 use Lower Flammability Limit (LFL), while gas detection and most plant practice use LEL. The same holds for UEL and Upper Flammability Limit (UFL). This calculator reports LEL because that is the term most engineers search and most instruments display.
  • %LEL expresses how close a mixture is to its lower limit. A reading of 100 %LEL means the fuel concentration equals the LEL and the mixture will burn if enough oxygen is present. A reading of 25 %LEL means one quarter of that concentration. The scale is linear: for methane, 25 %LEL is 1.25 vol% and 50 %LEL is 2.5 vol%.
  • The Limiting Oxygen Concentration (LOC) is the oxygen concentration below which a fuel, air, and inert mixture will not propagate flame no matter how much fuel is present. It is the basis for inerting under NFPA 69. A stream above 100 %LEL is still non-flammable if its oxygen content is below the LOC, which is why the calculator reports both numbers.

How the Calculator Computes Mixture LEL and LOC

A waste gas stream rarely contains a single fuel. The calculator combines the LEL of each combustible component with Le Chatelier's mixing rule, the method NFPA 69 recognizes for estimating the flammability limits of mixtures:

LEL of mixture = 100 / (y1/LEL1 + y2/LEL2 + ... + yn/LELn)

Here y1 through yn are the percentages of each combustible on a fuel-only basis (they sum to 100) and LEL1 through LELn are the individual limits in vol%. Nitrogen, carbon dioxide, water vapor, and any unentered balance are treated as inert, which is why the vol% fields do not need to add to 100.

The %LEL of the mixture is then the total combustible concentration divided by the mixture LEL:

%LEL = (total combustible vol% / mixture LEL vol%) x 100

Worked Example:

A stream carrying 1.0 vol% methane (LEL 5.0) and 1.0 vol% propane (LEL 2.1) with the balance air. On a fuel-only basis each is 50%. Mixture LEL = 100 / (50/5.0 + 50/2.1) = 100 / 33.8 = 2.96 vol%. Total combustibles are 2.0 vol%, so the stream is at 2.0 / 2.96 x 100 = 68 %LEL. That is above the 25 %LEL level that requires continuous monitoring and above the 50 %LEL level at which the stream must be interlocked out of the oxidizer, so it would need dilution air to bring it below 50 %LEL, plus continuous monitoring, before it enters a thermal oxidizer.

The LOC of the mixture is estimated with NFPA 69 B.8.1 Method 1, which multiplies the mixture's composite LEL by the stoichiometric oxygen required, with each combustible weighted by its share of the fuel. Here that is 2.96 x (0.5 x 2 + 0.5 x 5) = 10.35 vol% oxygen. With the balance as air, the stream holds about 20% oxygen, well above the LOC, which is why dilution rather than inerting is the practical control. Both results are evaluated at ambient temperature and pressure. Flammability limits widen as temperature rises, so a stream that is lean at ambient conditions sits at a higher %LEL at oxidizer inlet temperature. That is one reason the output is an estimate and not a design value.

Converting %LEL to Vol% and PPM

Instruments report in %LEL, permits and safety data sheets often use ppm, and process engineers work in vol%. The three are linked through the LEL of the gas in question, so the conversion is different for every compound.

  • vol% = %LEL x LEL (vol%) / 100
  • ppm = vol% x 10,000
  • %LEL = vol% / LEL (vol%) x 100

For methane, with an LEL of 5.0 vol%, the scale works out as follows.

%LEL Vol% Methane PPM Methane
1 0.05 500
10 0.5 5,000
20 1.0 10,000
25 1.25 12,500
50 2.5 25,000
100 5.0 50,000

The same 25 %LEL reading on propane (LEL 2.1 vol%) is only 0.525 vol%, or 5,250 ppm. Always convert with the LEL of the actual gas, or with the composite LEL from the calculator above for a mixture.

Does Oxygen Have an LEL?

No. An LEL applies to a fuel, and oxygen is the oxidizer, so there is no LEL or UEL for oxygen itself. When engineers ask for the LEL of oxygen they usually mean one of two other numbers.

  1. The first is the Limiting Oxygen Concentration. For most hydrocarbons the LOC with nitrogen as the inert is 10 to 12 vol% oxygen; for hydrogen it is about 4.6 vol% and for carbon monoxide about 5.1 vol%. Below the LOC the mixture cannot propagate flame at any fuel concentration. This is the value the calculator reports as LOC% Mixture.
  2. The second is the oxygen content of the waste gas itself. Oxidizer design needs enough oxygen to complete combustion, and PCC's thermal oxidizers add ambient air when the stream is oxygen-deficient.

LEL, UEL, and LOC of Common Gases

Values are in vol% in air at ambient conditions. LEL and LOC values match the calculator above. UEL values follow the NIOSH Pocket Guide. LOC values use nitrogen as the inert and reflect current test data under ASTM E2079, which is lower and more conservative than the older flammability-tube values. Natural gas has no single limit because its composition varies, but pipeline gas is mostly methane and is normally designed to methane's limits. The calculator above holds more than 120 compounds, including every gas listed here except natural gas, acetylene and gasoline.

Gas Formula LEL (vol%) UEL (vol%) LOC (vol% oxygen, nitrogen inert)
✓Methane CH4 5.0 15.0 11.1
✓Natural gas (pipeline) mostly CH4 about 5 about 15 about 11
✓Ethane C2H6 3.0 12.5 9.5
✓Propane C3H8 2.1 9.5 10.7
✓n-Butane C4H10 1.6 8.4 10.6
✓n-Hexane C6H14 1.2 7.5 10.4
✓Ethylene (ethene) C2H4 2.7 36.0 8.5
✓Propylene (propene) C3H6 2.15 11.1 10.0
✓Acetylene C2H2 2.5 100 n/a (can decompose without oxygen)
✓Hydrogen H2 4.0 75.0 4.6
✓Carbon monoxide CO 12.5 74.0 5.1
✓Hydrogen sulfide H2S 4.0 44.0 6.4
✓Ammonia NH3 15.0 28.0 about 11 (estimated)
✓Methanol CH3OH 7.18 36.0 8.5
✓Ethanol C2H5OH 3.3 19.0 8.7
✓Acetone C3H6O 2.6 12.8 10.0
✓Methyl ethyl ketone C4H8O 1.8 11.4 9.5
✓Benzene C6H6 1.2 7.8 11.4
✓Toluene C7H8 1.1 7.1 9.5
✓Styrene C8H8 1.1 6.8 9.0
✓Gasoline mixture 1.4 7.6 varies by blend (no single current value)

A compound with a low LEL, such as styrene or hexane, reaches 25 %LEL at a fraction of a percent by volume. A compound with a high LEL, such as ammonia or carbon monoxide, needs far more concentration to become flammable but is often the governing toxic limit long before that. Flammability and toxicity are separate questions; this page addresses the first.

Why Thermal Oxidizer Design Stops at 25 %LEL

NFPA 86 limits the fuel concentration entering an oxidizer to 25 %LEL unless the stream is continuously monitored, and to 50 %LEL with continuous LFL monitoring and safety interlocks. The calculator above tells you where a stream sits against those limits. The design answer depends on which side of them it lands.

  • Below 25 %LEL: Most solvent, coating, and process vent streams land here. The stream carries little fuel value, so the oxidizer needs heat recovery to keep fuel cost down. A regenerative thermal oxidizer recovers most of its exhaust heat through ceramic media and is the usual choice for high-volume, lean streams. Run the RTO Design and Cost Calculator to size one.
  • Between 25 and 50 %LEL: The stream must be continuously monitored, or diluted with ambient air until it drops below 25 %LEL. Dilution raises the total flow and therefore the size of the oxidizer, so the trade-off is monitoring cost against equipment cost. Streams in this range often carry enough heat to run with little or no supplemental fuel; the Heat Release Calculator shows how much.
  • Above 50 %LEL: The stream is treated as a fuel rather than a dilute waste gas. Options include a direct-fired thermal oxidizer engineered to burn it as fuel, a flameless thermal oxidizer, which mixes waste gas with air inside an inert ceramic bed , or a vapor combustor for intermittent vent and loading streams. Some streams are inerted below their LOC under NFPA 69 instead of being diluted; the calculator's LOC output is the starting point for that evaluation.

Every PCC system is custom engineered to the stream, so the %LEL result is the start of the conversation, not the end. A PCC engineering study confirms the flammability basis at operating temperature, sets the dilution or monitoring strategy, and sizes the system.

Other Common Questions

Need a Design-Basis Flammability Assessment?

The calculator is a screening tool. For a design-basis assessment, PCC's combustion engineers in Pittsburgh evaluate the full stream at operating conditions, set the dilution or monitoring approach, and size the system.

Request an engineering consultation or call 1 (412) 655-0955. Since 1969, PCC has engineered thermal oxidizers, flares, and vapor combustors for lean process vents and rich vent gas alike.